A data centre process water tank is selected by its worst stream, not its average one: cooling make-up with biocides, RO reject with high dissolved solids and scaling ions, concentrated chemical dosing solutions, and demineralised water that corrodes bare steel. The lining is chosen per duty, and a shared vessel is divided so the most aggressive stream cannot reach a compartment it would damage.
A data centre process water tank is defined by what it holds, and the contents of a data centre process loop are rarely just water. The same vessel family may carry cooling make-up, the concentrated reject from a reverse-osmosis (RO) plant, chemical dosing solutions used to keep the cooling system clean, and demineralised water for the highest-purity duties, and each of those streams attacks a tank lining through a different mechanism. The engineer specifying the tank is really specifying a material that survives the most aggressive chemistry in the loop, not the average.
This article works duty by duty: the chemistry of each process stream, the damage mechanism it creates for the lining, and the material choice that matches it. It cites NSF/ANSI/CAN 61 for potable contact, AWWA D102 for the coating of steel water-storage tanks, and AMPP SP 16 for the internal protection of water-storage tanks, and it closes with a selection table and the limits of that table when a duty sits outside its assumptions.
A data centre process water tank can hold any of several streams, and the duties overlap on a single campus. Cooling make-up replenishes the evaporative cooling loop and is the largest volume. Reverse-osmosis reject is the concentrated brine the on-site water treatment plant rejects, which is frequently routed to a tank for controlled discharge or reuse. Chemical dosing solutions are the biocides, scale inhibitors and pH-control acids held in day tanks before they are metered into the loop. Demineralised or ultrapure water serves humidification, make-up to sensitive equipment, or instrument supply where conductivity has to stay low.
The point that governs material selection is that these duties never share the same aggressiveness. A tank that is bought for soft cooling make-up can be destroyed by a year of RO reject or by a bulk chemical spill if the lining was not specified for it. The specification therefore has to name the worst credible stream the tank will see, and the lining decision follows that worst case rather than the duty printed on the purchase order.
Cooling make-up starts as the site supply water, but by the time it sits in the loop it carries the chemistry the treatment programme adds. The control targets are pH, alkalinity, calcium hardness and conductivity, held inside a range that limits scaling and corrosion, and a biocide is maintained to suppress Legionella and general fouling. Oxidising biocides such as chlorine or bromine, and non-oxidising alternatives, are present at low but continuous concentration, and a side-stream filtration loop keeps suspended solids down.
For the tank lining this is a moderate duty. The water is aerated, the pH is controlled rather than extreme, and the biocide concentration is low, but it is persistent, so a coating qualified to AWWA D102 for welded steel, or one of the factory coating systems permitted by AWWA D103 for bolted tanks, is the baseline. The failure mode is gradual: pinholing where the coating is thin or damaged, then under-film corrosion spreading from the holiday. The lining has to survive years of continuous wetting and drying at the operating level, not a single fill.
RO reject is the opposite of benign. It is the concentrate stream from a reverse-osmosis plant, so its total dissolved solids, conductivity and scaling-ion concentration (calcium, magnesium, sulfate, silica, barium) are several times the feed. It is often acidic from the antiscalant and pH programme, and its chloride content can be high. That combination is exactly what drives pitting and crevice corrosion in carbon steel and what stresses an organic lining through osmotic blistering if the lining is permeable.
The damage mechanism is twofold. Chemically, high chloride and low pH attack any exposed steel and exploit coating defects. Physically, a permeable lining absorbs the concentrated solution and blisters as osmotic pressure builds behind it, which is why a holiday-free, low-permeability system matters more here than for cooling make-up. A tank that sees RO reject should be lined for the worst reject analysis on record, not the average, and the operating level and any vapour space should both be protected because crystallisation at the waterline can cut a lining that is only rated for immersion.
Chemical dosing duty is the most locally aggressive because the tank holds concentrated product, not a diluted loop. Biocide day tanks, acid day tanks for pH or scale control, and antiscalant or coagulant solutions are stored at concentrations far above what the loop sees, and a spill, an overfill or a cleaning event can expose the lining to full-strength chemical. Sulfuric or hydrochloric acid, sodium hypochlorite and similar oxidisers each demand a lining proven against that specific reagent.
The material response is to match the lining to the reagent, and where the reagent is too aggressive for a coated steel tank, stainless steel or a non-metallic such as high-density polyethylene or fibreglass-reinforced plastic is the candidate, with the choice made against the chemical compatibility data for that reagent and concentration. The failure mode is rapid: a lining dissolved or swollen by a reagent it was never rated for fails in months, not years. The dosing tank is therefore specified from the chemical's safety data sheet and compatibility table, not from a generic water-tank lining list.
Demineralised and ultrapure water present a deceptively gentle but real corrosion problem. With the hardness and dissolved solids removed, the water no longer deposits the protective films that limit attack on carbon steel, so bare steel corrodes and the corrosion products raise the conductivity the ultrapure duty is trying to keep low. The water is also aggressive to some organic linings because of its solvency, and it can leach components from a lining that is not rated for it.
The material answer is to keep demineralised water away from bare steel and from linings that can contaminate it. Stainless steel such as 316L is a common choice for ultrapure duty, and a tank built to NSF/ANSI/CAN 61 is required if the demineralised stream contacts potable or potable-adjacent service. Where steel is used with a lining, the lining has to be one documented as suitable for demineralised service, because a lining chosen for raw water will not necessarily hold up. The constraint is purity as much as corrosion: the tank cannot be the source of the ions the process is removing.
The selection rule is to let the worst duty set the lining, and to specify the lining by name rather than by a performance promise. For cooling make-up and general process duty, a coating system qualified to AWWA D102 (welded) or AWWA D103 factory systems (bolted) is the baseline, and AMPP SP 16 guides the internal protection specification and the surface preparation it depends on. For demineralised service, stainless or a demineralised-rated lining is chosen, and for chemical dosing the reagent compatibility table decides.
Steel is not the only option, and the non-metallic route is covered separately, but the principle is the same: the lining or material is matched to the worst credible stream. NSF/ANSI/CAN 61 conformance is required for any wetted component that contacts potable or potable-adjacent water, and that conformance is a documented requirement, not a coating claim. A tank bought for one duty and later fed a worse one is the common failure, which is why the specification names the full set of streams the vessel may receive.
Where several process duties share one shell, the way to keep an aggressive stream from a sensitive one is to divide the tank internally. A baffle wall or separate compartments hold the duties apart while sharing the foundation, roof and shell, and the division has to be detailed so the streams cannot mix at the waterline, through the wall, or during cleaning and filling. The fire and potable separations covered elsewhere still apply, but within the process side the issue is chemical compatibility rather than code separation.
The design discipline is to treat each compartment as its own tank for lining selection. The RO reject compartment gets the low-permeability, chemical-resistant lining; the demineralised compartment gets stainless or a demineralised-rated lining; the cooling make-up compartment gets the baseline system. The dividing structure, its penetrations and its supports also have to be designed for the differential heads and the different chemistries on each side, and the specification names the lining per compartment so the fabricator cannot coat the whole shell with one system.
A duty-to-material table is a useful first filter, but it has limits a reviewer should respect. The table answers the common cases: cooling make-up to a coated steel or glass-fused-to-steel tank, RO reject to a chemical-resistant low-permeability lining, demineralised to stainless or a demineralised-rated lining, and chemical dosing to the reagent-compatible material. It tells you where to start, not where to stop.
The limits appear when a duty sits outside the table's assumptions. A reject stream whose analysis is not on record, a blended stream whose chemistry changes with plant mode, or a chemical whose concentration exceeds the lining's rated range all require the actual data rather than the table entry. The table also cannot substitute for the coating application quality, the surface preparation to AMPP SP 16, and the holiday testing that decide whether the named system actually performs. Use the table to scope the enquiry, then require the analysis, the compatibility data and the application records for the specific streams in hand.
Duty | Key chemistry | Damage mechanism | Lining or material |
Cooling make-up | Controlled pH, biocide, low solids | Gradual pinholing and under-film corrosion | AWWA D102 coating or AWWA D103 factory system |
RO reject | High TDS, high chloride, low pH, scaling ions | Pitting, crevice corrosion, osmotic blistering | Low-permeability chemical-resistant lining |
Chemical dosing (concentrated) | Full-strength reagent by SDS | Rapid dissolution or swelling of unrated lining | Reagent-compatible: stainless, HDPE or FRP |
Demineralised / ultrapure | Near-zero hardness and solids | Steel corrosion, lining leaching, conductivity rise | 316L stainless or demineralised-rated lining |
Potable-adjacent | Drinking-quality | Contamination if non-conforming | NSF/ANSI/CAN 61 wetted components |
Stream | Cause | Symptom | Mitigation |
Cooling make-up | Persistent low-level biocide, wet/dry cycles | Pinholes, under-film rust | Holiday-free AWWA D102 or D103 lining, level protected |
RO reject | High chloride, low pH, permeability | Pits at defects, osmotic blisters | Low-permeability lining, full immersion plus waterline rated |
Chemical dosing | Concentrated reagent contact | Dissolved or swollen lining | Reagent compatibility table; stainless, HDPE or FRP |
Demineralised | No protective films, solvency | Steel loss, ion pickup | 316L or demineralised-rated lining; no bare steel |
Blended or variable | Changing plant-mode chemistry | Unpredictable attack | Require actual analysis; do not use table default |
No matching project record exists in the verified project library for a data centre process water tank carrying cooling make-up, reverse-osmosis reject and chemical dosing, and no project reference is given on this page. The recommendations above rest on the duty-by-duty chemistry and damage mechanisms, the lining selection rule that the worst stream sets the material, and the references NSF/ANSI/CAN 61, AWWA D102 and AMPP SP 16. For a specific site, the selection table and the compatibility and analysis records set out here form the basis a reviewer can audit.
Center Enamel (Shijiazhuang Zhengzhong Technology Co., Ltd.) designs and fabricates bolted steel storage tanks, welded steel tanks, fusion-bonded epoxy tanks, galvanized tanks, stainless steel vessels, pressure vessels, aluminum geodesic dome roofs and floating roofs. The company has more than 30 years of production experience and has supplied equipment to projects in more than 100 countries. Aluminum geodesic dome roofs are designed and fabricated to API 650 Appendix G, AWWA D108, the Aluminum Design Manual, ASCE 7 and IBC, and the company developed and exported a 72 m diameter aluminum dome roof in 2023. Engineering, fabrication, coating, quality control and site service are handled as one scope, which is why the drawings, the calculation basis and the delivered hardware can be reconciled against each other.
What duties does a data centre process water tank handle?
A data centre process water tank can hold cooling make-up for the evaporative cooling loop, reverse-osmosis reject from the on-site water treatment plant, chemical dosing solutions such as biocides, scale inhibitors and pH-control acids, and demineralised or ultrapure water for humidification or sensitive make-up. Each stream attacks a lining through a different mechanism, so the tank is specified for the worst credible stream it will see, not the average duty printed on the purchase order.
How does RO reject affect a tank lining?
RO reject is the concentrated brine from a reverse-osmosis plant, so its total dissolved solids, chloride and scaling ions such as calcium, magnesium, sulfate and silica are several times the feed, and it is often acidic. High chloride and low pH drive pitting and crevice corrosion in any exposed steel, and a permeable lining blisters osmotically as the concentrate is drawn behind it. A tank seeing reject needs a low-permeability, holiday-free lining rated for the worst reject analysis, with the waterline protected against crystallisation cutting the coating.
Which material suits chemical dosing duty?
Chemical dosing duty holds concentrated product, so the material is matched to the reagent from its safety data sheet and compatibility table rather than a generic water-tank lining. Acid day tanks, biocide day tanks and antiscalant solutions each need a lining proven against that specific reagent and concentration; where the reagent is too aggressive for coated steel, stainless steel or a non-metallic such as high-density polyethylene or fibreglass-reinforced plastic is the candidate. The failure mode is rapid dissolution or swelling of an unrated lining.
Can a process water tank be shared between duties?
A process water tank can be shared between compatible duties if it is divided internally so the streams cannot mix. Each compartment is then lined for its own duty: the reverse-osmosis reject compartment gets a chemical-resistant low-permeability lining, the demineralised compartment gets stainless or a demineralised-rated lining, and the cooling make-up compartment gets the baseline system. The division must be detailed against differential heads and the different chemistries on each side, and the specification names the lining per compartment.
What is the difference between make-up and reject water?
Make-up water is the relatively clean supply added to replace losses from evaporation and blowdown in the cooling loop, carrying the treatment chemistry at low, controlled concentration. Reject water is the concentrated waste stream a reverse-osmosis plant discharges, with total dissolved solids, chloride and scaling ions multiplied several times and often acidic. Make-up is a moderate lining duty; reject is one of the most aggressive streams a process tank will see and needs a chemical-resistant, low-permeability lining.
What lining suits demineralised water service?
Demineralised water removes the hardness and dissolved solids that protect carbon steel, so bare steel corrodes and raises the conductivity the duty is meant to keep low, and some organic linings are leached or swollen by its solvency. The answer is to keep demineralised water away from bare steel and unrated linings: stainless steel such as 316L, or a tank with a lining documented as suitable for demineralised service. If the stream contacts potable or potable-adjacent service, NSF/ANSI/CAN 61 conformance is required for the wetted components.
How should compartments be designed?
Compartments should be detailed as independent tanks for lining selection while sharing the shell, roof and foundation. The dividing wall and its penetrations must prevent mixing at the waterline, through the wall, or during cleaning, and the structure has to carry the differential heads and differing chemistries on each side. The specification names the lining per compartment so the fabricator cannot coat the whole shell with one system, and the surface preparation and holiday testing are required to the same standard as a single-duty tank.
A data centre process water tank is selected by its worst stream, and the lining decision is made once that worst credible chemistry is named. Cooling make-up is a moderate duty, RO reject is among the most aggressive, concentrated chemical dosing is locally the harshest, and demineralised water corrodes the steel it is meant to protect. The lining is specified by name to AWWA D102, AWWA D103 or a reagent-compatible system, and NSF/ANSI/CAN 61 is required wherever potable contact is in scope.
Where duties share a shell, the tank is divided and each compartment is lined for its own chemistry, with the division detailed against differential heads. Send us the full list of streams the vessel may receive, the reject analysis, the chemical compatibility data and the potable contact requirement, and we will return a tank specification that names the lining per duty and the records that prove it.
Send the duty, the volume basis, the governing code and the site constraints, and our engineering team will come back with a specification that a supplier can price and a reviewer can approve. We will also tell you plainly when a different tank type or a different scope is the better answer.
1. NSF/ANSI/CAN 61, Drinking Water System Components
2. AWWA D102, Coating Steel Water-Storage Tanks
3. AMPP SP 16, Internal Protection of Water-Storage Tanks