Cooling Tower Water Storage Tank For A Data Centre: Water Balance And Corrosion Control

3_2.jpg

Cooling Tower Water Storage Tank For A Data Centre: Water Balance And Corrosion Control

A cooling tower make-up tank is sized from the water balance, not from a rule of thumb: make-up M equals evaporation E times the cycles-of-concentration ratio CoC/(CoC−1), and the reservoir holds the autonomy the site needs against supply interruption and treatment cycling. Higher cycles concentrate dissolved solids, raising scaling and corrosion risk, so the tank and the treatment programme are designed together.

Introduction

A data centre cooling tower is a water-balancing device as much as a heat rejecter. Water enters as make-up, leaves as evaporation, blowdown, drift and windage, and the ratio between what goes in and what is deliberately discharged — the cycles of concentration — sets both the water bill and the corrosion and scaling risk in the loop. The make-up tank is where that balance is fed and buffered, and its size and features decide how controllable the balance is.

 

This article builds the water balance from first principles, shows how the make-up demand follows from evaporation and the chosen cycles of concentration, and explains how the reservoir is sized and what tank features keep the balance under control. It cites the ASHRAE Handbook — HVAC Systems and Equipment, the ASSP 3 guidance on industrial water treatment for cooling systems, and NSF/ANSI/CAN 61 where the make-up source is potable.

The cooling water balance

The cooling water balance is an accounting of every stream crossing the cooling system boundary. Make-up M is what you add; evaporation E, blowdown B, drift D and windage or leakage W are what you lose, and at steady state M = E + B + D + W. Evaporation is the useful loss that carries heat away; blowdown is the deliberate discharge that controls concentration; drift and windage are unintended losses; leakage is a defect to be eliminated.

The balance matters because it links the heat rejection duty to the water footprint and to the chemistry. The make-up tank sits on the M side of the equation, and its job is to supply M reliably and to buffer the variations in supply and demand so the tower never runs short. The balance also defines the cycles of concentration, the single number that sets how aggressive the water becomes, and therefore how the tank and the treatment system have to perform.

Evaporation and its drivers

Evaporation is driven by the heat rejected and by the temperature range across the tower. The long-established approximation is that about 0.8 percent of the recirculation flow evaporates for every 10°F (5.6°C) of range, so E ≈ 0.008 × Q × (range / 10°F), where Q is the recirculated flow. In SI terms the evaporation is roughly proportional to Q and to the range ΔT, and the proportionality is set by the latent heat of vaporisation.

The drivers are therefore the cooling load and the approach/range the tower is asked to deliver. A data centre running at high and steady IT load keeps E near-constant day to day, which is what makes the make-up demand predictable; the variation comes from wet-bulb swings across the year, because a warmer, more humid ambient reduces the achievable range and changes the evaporation fraction. The make-up tank has to cover the peak-week evaporation, not the annual average, because the loop cannot run short during the worst cooling conditions.

Blowdown and cycles of concentration

Blowdown is the discharge you control to keep the dissolved solids in the loop from climbing without limit. The cycles of concentration (CoC) is the ratio of a tracer in the circulating water to the same tracer in the make-up, so CoC = M / (B + D) at steady state, where D is drift. In practice, with drift small, CoC ≈ M / B, and the higher the CoC the less blowdown you discharge for a given make-up.

The trade is direct: raising CoC cuts blowdown and therefore make-up and sewer discharge, which is the water-saving lever, but it also concentrates calcium, alkalinity, sulfate and chloride, which raises scaling and corrosion risk. There is a practical ceiling, often around 3 to 6 cycles for many open recirculating systems, set by the scaling potential of the make-up and the tolerance of the treatment programme. The make-up tank feeds the loop that the blowdown valve is trying to keep in balance, so its level control and the blowdown setpoint have to be coordinated.

Make-up demand from the balance

The make-up demand follows straight from the two previous sections. From the balance M = E + B + D + W, and from the cycles relation B + D = M / CoC, so combining gives M = E / (1 − 1/CoC) = E × CoC / (CoC − 1). For a given evaporation, doubling the cycles from 3 to 6 cuts make-up by about a third, because the denominator grows while E stays fixed.

This is the calculation a reviewer wants: state E from the load and range, state the target CoC from the water chemistry and treatment limit, and compute M. The data centre duty cycle helps here because E is steady, so M is a number you can defend rather than a seasonal guess. Windage and leakage are added as corrections, and leakage in particular should be zero by design and verified, because an unmetered leak inflates the make-up you have to size for and hides a defect.

Sizing the make-up reservoir

The reservoir is not sized by the hourly make-up rate alone; it is sized by the autonomy the site needs. A common basis is to hold several hours to a full day of average make-up demand so that a municipal supply interruption, a softener regeneration or a reverse-osmosis cleaning event does not starve the tower. The tank also buffers the make-up pump cycling and gives the treatment system retention so chemicals are dosed against a stable supply rather than a fluctuating one.

The sizing inputs are the computed M, the required autonomy time, and any minimum volume the treatment system needs for its own retention. The usable volume, not the gross volume, is what counts, because the tank has a dead bottom it cannot draw from and a high level it should not exceed. The design basis should state which of those it is using, and the reserve should be checked against the worst-week make-up, not the annual average, because the tower cannot be allowed to run dry during peak cooling.

Corrosion, scaling and microbiological control

The cycles of concentration decide the chemistry the loop has to survive. Scaling ions such as calcium and bicarbonate concentrate as CoC rises, so calcium carbonate precipitation on heat-exchange surfaces becomes the limiting risk; the treatment programme controls this with pH management and scale inhibitors and by not pushing CoC past the water's scaling threshold. Corrosion rises with concentrated chloride and with low or poorly controlled pH, so the programme also holds a corrosion inhibitor and a pH band.

Microbiological control, including Legionella, depends on keeping the system moving and treated; the make-up tank itself is a stagnation point if it is oversized and barely turns over, so it should be sized no larger than the autonomy requires and fitted to keep water moving and screened from contamination. The tank interior is coated to AWWA D102 (welded) or a factory system permitted by AWWA D103 (bolted) so iron pickup does not add to the fouling load, and any potable make-up source carries NSF/ANSI/CAN 61 conformance for wetted components.

Tank features that make the balance controllable

A make-up tank that supports the balance has specific features rather than a plain open box. Level instrumentation with high and low alarms lets the make-up valve and the treatment system respond before the tower runs short. A screened and vented opening keeps debris and vermin out without trapping gases. A bottom slope and a full drain let the tank be emptied and cleaned, which links to the microbiological control above.

The overflow must be sized for the maximum fill rate and discharge clear of the foundation, and the make-up connection should be arranged so treatment chemicals are introduced into a moving stream, not a stagnant corner. A by-pass for the softener or reverse-osmosis plant, and a metered connection to the blowdown and make-up flows, turns the tank from a passive reservoir into the measurement and dosing point of the whole balance. These features are what let the operator actually hold the target CoC instead of guessing.

Where the tank meets the treatment system

The make-up tank is the interface between the water supply and the cooling loop, and the treatment system lives at that interface. The softener, reverse-osmosis unit or other preconditioning feeds the tank; the scale and corrosion inhibitors and the biocide are dosed into the make-up stream or the tank suction; and the blowdown is metered from the loop back past the tank. The tank gives each of those functions a stable, buffered volume to work against.

The design question is where the control points sit. If the treatment is dosed on make-up flow, the tank buffers the dosing against pump cycling; if it is dosed on recirculation, the tank still sets the chemistry of what enters. The coordination that matters is between the tank level control, the blowdown setpoint and the CoC measurement, because together they hold the balance the ASHRAE and ASSP 3 guidance describes. A tank specified without its place in that loop is a tank that cannot deliver the cycles it was sized for.

Water Balance: Stream, Symbol, Meaning, Effect

Stream

Symbol

What it is

Effect on balance

Make-up

M

Water added to the system

Inflow the tank supplies

Evaporation

E

Useful heat-loss vaporisation

Outflow; sets minimum make-up

Blowdown

B

Deliberate concentrated discharge

Outflow that controls CoC

Drift

D

Entrained droplets from the tower

Unintended outflow; small

Windage or leakage

W

Spray loss or defect leak

Outflow to eliminate by design

Cycles Of Concentration And The Trade It Imposes

Cycles (CoC)

Blowdown fraction (1/CoC)

Relative make-up (CoC/(CoC-1))

Consequence

2

0.50

2.00× evaporation

High water use, low concentration

3

0.33

1.50× evaporation

Moderate use, manageable chemistry

4

0.25

1.33× evaporation

Lower use, scaling risk rising

6

0.17

1.20× evaporation

Low use, tight treatment control needed

Above threshold

—

—

Scaling or corrosion limits reached

Project Reference

No matching project record exists in the verified project library for a data centre cooling tower make-up reservoir sized by water balance, and no project reference is given on this page. The recommendations above rest on the steady-state balance M = E + B + D + W, the cycles-of-concentration relation, the make-up formula M = E·CoC/(CoC−1), and the ASHRAE Handbook, ASSP 3 and NSF/ANSI/CAN 61 references. For a specific site, the evaporation, target cycles and autonomy inputs set out here form the calculation a reviewer can audit.

About Center Enamel

Center Enamel (Shijiazhuang Zhengzhong Technology Co., Ltd.) designs and fabricates bolted steel storage tanks, welded steel tanks, fusion-bonded epoxy tanks, galvanized tanks, stainless steel vessels, pressure vessels, aluminum geodesic dome roofs and floating roofs. The company has more than 30 years of production experience and has supplied equipment to projects in more than 100 countries. Aluminum geodesic dome roofs are designed and fabricated to API 650 Appendix G, AWWA D108, the Aluminum Design Manual, ASCE 7 and IBC, and the company developed and exported a 72 m diameter aluminum dome roof in 2023. Engineering, fabrication, coating, quality control and site service are handled as one scope, which is why the drawings, the calculation basis and the delivered hardware can be reconciled against each other.

Frequently Asked Questions

How is cooling tower make-up water calculated?

The make-up is found from the water balance M = E + B + D + W, where E is evaporation, B is blowdown, D is drift and W is windage or leakage, and from the cycles relation B + D = M / CoC. Combining them gives M = E × CoC / (CoC − 1): you compute evaporation from the rejected heat and the tower range, choose the target cycles of concentration from the water chemistry, and divide. State each term and the leakage term should be zero by design; an unmetered leak inflates the make-up you size for.

What are cycles of concentration?

Cycles of concentration is the ratio of a dissolved tracer in the cooling loop to the same tracer in the make-up water, so CoC = M / (B + D) at steady state. It measures how many times the incoming water has been effectively concentrated by evaporation. A higher CoC means less blowdown and lower water use, but it also concentrates scaling ions and chlorides, so the practical ceiling is set by the make-up water's scaling potential and the treatment programme's tolerance, commonly around 3 to 6 cycles.

How much make-up water does a cooling tower need?

The make-up equals evaporation divided by (1 − 1/CoC), so it is set by the evaporation rate and the chosen cycles of concentration rather than by the tower size alone. Evaporation is roughly 0.8 percent of recirculation per 10°F of range, and a data centre's steady IT load keeps that near-constant, which makes the demand predictable. Raising cycles from 3 to 6 cuts make-up by about a third; the figure to size for is the worst-week evaporation, not the annual average.

What size should the make-up water tank be?

The reservoir is sized for the autonomy the site needs, typically several hours to a day of average make-up, so a supply interruption, softener regeneration or reverse-osmosis cleaning does not starve the tower, plus any retention the treatment system requires. Use the usable volume, not gross, because the tank has a dead bottom and a high-level limit. Check the reserve against the worst-week make-up demand, and avoid oversizing, because an oversized tank turns over slowly and becomes a stagnation point.

How does cycles of concentration affect corrosion?

As cycles rise, chloride, sulfate and the corrosivity of the loop concentrate along with the scaling ions, and corrosion risk grows if pH and inhibitors are not held in band; at the same time calcium and bicarbonate concentrate, raising scaling risk. The treatment programme manages both by controlling pH, adding scale and corrosion inhibitors, and not exceeding the water's scaling threshold. The tank and treatment system are designed together, because the CoC the loop runs at is the chemistry both have to survive.

What tank features help control the water balance?

A controllable make-up tank has level instrumentation with high and low alarms, a screened and vented opening, a sloped bottom and full drain for cleaning, an overflow sized for the maximum fill rate, and a make-up connection that introduces treatment chemicals into a moving stream. A by-pass for the softener or reverse-osmosis plant and metered make-up and blowdown connections turn the tank into the measurement and dosing point of the balance, letting the operator hold the target cycles of concentration.

How does the make-up tank connect to the treatment plant?

The tank is the interface between supply and loop: the softener, reverse-osmosis unit or other preconditioning feeds it, scale and corrosion inhibitors and biocide are dosed into the make-up stream or tank suction, and blowdown is metered from the loop. The tank buffers the dosing against pump cycling and gives each function a stable volume. The key coordination is between tank level control, the blowdown setpoint and the cycles-of-concentration measurement, which together hold the balance the cooling-system guidance describes.

Conclusion

A data centre cooling tower make-up tank is an instrument of the water balance, not a convenience tank. The balance M = E + B + D + W and the cycles relation give a single defensible make-up figure, M = E × CoC / (CoC − 1), and the reservoir is then sized for the autonomy the site needs, using usable volume against the worst-week demand.

 

The cycles of concentration tie the water saving to the corrosion and scaling risk, so the tank and the treatment programme are one design. Level control, screened vents, a drain, a sized overflow and a metered connection to the treatment system turn the tank into the controllable point of the whole loop. Send us the rejected heat, the tower range, the make-up water analysis and the autonomy requirement, and we will return a tank sized from the balance with the features that keep it under control.